Marsh’s Inverted Bucket Traps provides efficient condensate drainage for
all steam equipment. Reliability and ruggedly constructed, our Bucket Trap
allows for minimal repair, maintenance or labor related costs.
Usages:
• Oil Pre-heaters
• Converters
• Steam Cookers
• Dryers
• High-Pressure Drip
• Laundry Equipment
• Process Equipment
Features:
• High Strength Cast Iron Body
• Hardened Stainless Steel
Valve & Seat
• Stainless Steel Bucket
• Test Plug
• Low Maintenance
Materials:
• Body & Cover - Cast Iron-ASTM-A-126-7/Class B
• Bucket & Linkage - Stainless Steel
• Valve & Seat - Hardened Stainless Steel
• Standpipe - Steel Pipe
• Cover Gasket - Non-Asbestos As the system starts, air and non-condensable gases vent through the orifice
in the bucket; condensate also enters through the standpipe which forms a
water seal in the bottom of the bucket. When steam enters the trap a simple
lever mechanism attached to the inverted bucket snaps shut; then as the
steam condenses the buoyancy of the bucket changes thus opening the lever
mechanism, allowing pressure to force the condensate out of the trap. This
process repeats itself exactly and continuously to maximize the efficient use
of energy. No cooling leg required. Refer to capacity charts when ordering.
|
|
|
|
800
Series Dimensions and Capacities |
|
|
|
|
|